Rack Power Check Open the tool

See what goes dark when a power feed fails

Draw your racks, PDUs and power cords. Rack Power Check works out which devices lose power, and which breaker or bank is assumed to trip, when a feed, a PDU or a bank goes off. It runs in your browser: no account, and the room you draw is not uploaded.

Or the same rack with the problem fixed.

Switch a feed off to see what goes dark.

An example rack seen from the rear, with invented numbers, worked out by the tool's own calculation. Each square or circle is a power cord, in its feed's colour, at the end nearest the PDU it is plugged into.

What it shows

Switch a feed off and the racks show what happens. Devices with no power go dark. If the load that moves to the other PDU is more than a bank's breaker or the PDU's rating, the tool shows that part tripping, then checks again, because one trip can set off another. Every cord is drawn in its feed's colour and shape, so two cords on one PDU are easy to see.

What you can print

Rack elevations, front and rear, on A3 sheets. A device schedule with bank loads, a cabling list and single-line diagrams. A report with the verdict, what each feed going off does, and the findings. All of it comes from the room you drew.

Your equipment

A built-in library of about 4,600 device and PDU models fills in height, depth and number of cords. The figures come from a community-maintained list and can be wrong or missing, so a draw taken from it is marked as a label figure to check. Your own types can be saved for reuse.

Who it is for

People who look after a small server room, a comms room, a lab or a colocation cage and want to see the power paths in one drawing. A room can hold up to 24 racks.

What it assumes

  • Single-phase 230 VThree-phase supplies are not handled yet.
  • Ratings are not assumedA feed, PDU, bank or breaker rating is what you enter. Until a PDU has its rating, it is left out of the check and counted as not in the check yet.
  • Cords arrive unpluggedWhere each cord really goes is what is being checked, so the tool does not guess a tidy answer. A cord that is not plugged in keeps its device out of the check.
  • Feeds are not assumed independentTwo PDUs count as separate supplies only when you say they are on different feeds. "Not sure" puts them on one feed.
  • Nothing upstream is checkedWhat feeds your feeds is not seen: a UPS, a generator or a transfer switch is not modelled.
  • The 40 % target, on every bankIn a room with two or more feeds, every rated feed, PDU and bank above 40 % of its rating in normal running is reported, including a bank that would not take on more load if the other feed went off.
  • Over means aboveA part trips only when its load is above its rating; exactly 100 % does not trip. The 80 % limit is a setting.

Questions

Is it free?

Yes. There is nothing to sign up for.

Where does my room go?

Nowhere. It is kept in your browser on this device, and you can save it to a file. The tool's page is set so that it cannot send anything. If your browser blocks storage, the tool says it is not saving.

How accurate is it?

It is arithmetic on the numbers you enter. If a rating or a draw is wrong, the answer is wrong. It gives estimates only.

Can it take equipment that is not in the library?

Pick a model from the library, or enter your own height, number of cords and draw.

Does it work on a phone?

It is made for a laptop or desktop screen. It opens on a phone and the page scrolls, but placing equipment and following cords is easier with a mouse and a wider screen.

Does this site count visitors?

Yes. The server counts how often each page is opened, the tool's page included, with no cookies and nothing about you. What is typed into the tool or a calculator is not sent: it stays in your browser. The privacy page says exactly what is kept.